4824 - Aux (480-240 volt, 135 VA)
4824 - Aux (135 VA) - 480:240
This transformer is designed to provide auxiliary power where the application is 480V 3-wire delta. Applications include, but are not limited to, under-glass Aclara  PLC (TWACS®) transmitters or external three-phase Landis+Gyr (Hunt) endpoints .

This transformer is identical in its basic design to the ones used in our 2:1 VT Pack™ (Cat.# 6004824). The 4824-Aux provides the same protection against failure of the Aclara PLC (TWACS®) or Landis+Gyr (Hunt) endpoints as the VT Pack provides against failure of wide voltage range solid state meters.
Ratio2:1 (480:240 Volts)
Primary Voltage240-480 Volts
Over voltage withstand900V for 1 minute
Insulation level10kV BIL
Size3.5" Diameter, 2.6" Height
Lead Length24"
Lead Wire Size#14 Stranded
Weight3 lbs.
MountingInternal or External
VA Rating135 VA @ 30 degrees C; 85 VA @ 55 degrees C